01)

Where floodlights are installed on steel tower, the tower shall be equipped with steel service platforms located _____ below the fixtures  

Answer:

1.5m

02)

In industrial lighting, poles used in process areas shall be________ 

Answer:

Hot‐Dipped Galvanized

03)

Fixtures that shall be used for high‐bay or low‐bay indoor‐industrial applications –

Answer:

High‐Pressure Sodium or Metal Halide

04)

In manned switchgear rooms and control rooms, where essential activities continue during failure of normal lighting, a minimum illumination level of ______ shall be provided at 760mm above the floor.

Answer:

100 Lux (10 fc)

05)

An indoor location that shall be provided with enclosed and gasketed (i.e. vapor‐tight) corrosion resistant lighting fixtures.

Answer:

Battery Rooms

06)

Lighting Fixtures positioned over stairways, platforms, elevated walkways and landings shall be positioned at a height of _____ (from the bottom of the fixture to the floor directly beneath).

Answer:

             2.03m

07)

7 Minimum duration of emergency lighting in the event of power failure 

Answer:

              1.5hrs.

08)

Illuminated exit signs shall be manufactured and installed in accordance with ___________ requirements. 

Answer:

NFPA 101

09)

In SAES‐P‐123 lighting standards, what is the meaning of CRI? 

Answer:

Color Rendering Index

10)

IN SAES‐P‐123 lighting standards, what is the meaning of LLF? 

Answer:

Light Loss Factor

11)

Minimum maintained illuminance level of Control Room in general  500 Lux (50 fc)

Answer:

0

12)

Minimum maintained illuminance level of Process Interfaced Buildings 

Answer:

100 Lux (10 fc)

13)

Minimum maintained illuminance level of Battery Rooms 

Answer:

300 Lux (30 fc)

14)

Minimum maintained illuminance level of Switchgear Rooms 

Answer:

300 Lux (30 fc)

15)

Minimum maintained illuminance level of Outdoor Switchyards 

Answer:

20 Lux (2 fc)

16)

Minimum maintained illuminance level of General Substation (outdoor) 

Answer:

20 Lux (2 fc) .

17)

Minimum maintained illuminance level of General Substation (indoor)

Answer:

50 Lux (5 fc)

18)

Minimum maintained illuminance level of Indoor Substation Operating Aisle 

Answer:

150 Lux (15 fc)

19)

Minimum maintained illuminance level of Plant Process Areas

Answer:

50 Lux (5 fc)

20)

What is the meaning of CT 

Answer:

Current Transformer

21)

What is the meaning of VT

Answer:

              Voltage Transformer

22)

For transformer protection system, what is the meaning of 51N

Answer:

Neutral Overcurrent Relay

23)

For transformer protection system, what is the meaning of 50/51H 

Answer:

Phase Overcurrent Relay (HV side)

24)

For transformer protection system, what is the meaning of 50/51L

Answer:

Phase Overcurrent Relay (LV side)

25)

For transformer protection system, what is the meaning of 50/51G

Answer:

Ground Overcurrent Relay

26)

For transformer protection system, what is the meaning of 87 

Answer:

Differential Relays

27)

For transformer protection system, what is the meaning of 86 

Answer:

Lockout Relays

28)

Maximum ampere rating for panel board

Answer:

400A

29)

Maximum ampere rating for switch racks 

Answer:

600A

30)

Unobstructed horizontal space for switchgear

Answer:

Front=2m; back and sides=1m

31)

Unobstructed horizontal space for control gear, switchboards, transfer switches, and floor mounted adjustable frequency drives 

Answer:

Front=1.5m; Sides=1m

32)

Unobstructed horizontal space for panel boards, switch racks 

Answer:

Front=1m

33)

Cables can be used to extend the main bus of switchgear, control gear, switchboards, switch racks, and panel boards (TRUE or FALSE) 

Answer:

FALSE

34)

Maximum control voltage to be used for motor space heater 

Answer:

24V

35)

In Switchgear and control equipment system, What is the meaning of AFD

Answer:

Adjustable Frequency Drive

36)

Cable bus shall be used with power transformers if the forced cooled site rating of the transformer is greater than ________

Answer:

1200A

37)

Transfer switches shall only be used in low voltage applications (TRUE or FALSE

Answer:

TRUE

38)

Panel boards shall be installed completely filled with circuit breakers and have ______ spare breakers 

Answer:

0.2

39)

Panel boards shall not be installed in control gear (TRUE or FALSE)

Answer:

TRUE

40)

What is the meaning of abbreviation IEC?

Answer:

International Electro Technical Commission