List of Manpower Supply Companies in Saudi Arabia
01) |
Where floodlights are installed on
steel tower, the tower shall be equipped with steel service platforms located
_____ below the fixtures |
Answer: |
|
1.5m |
|
02) |
In industrial lighting, poles used in
process areas shall be________ |
Answer: |
|
Hot‐Dipped Galvanized |
|
03) |
Fixtures that shall be used for
high‐bay or low‐bay indoor‐industrial applications – |
Answer: |
|
High‐Pressure Sodium or Metal
Halide |
|
04) |
In manned switchgear rooms and
control rooms, where essential activities continue during failure of normal
lighting, a minimum illumination level of ______ shall be provided at 760mm
above the floor. |
Answer: |
|
100 Lux (10 fc) |
|
05) |
An indoor location that shall be
provided with enclosed and gasketed (i.e. vapor‐tight) corrosion resistant
lighting fixtures. |
Answer: |
|
Battery Rooms |
|
06) |
Lighting Fixtures positioned over
stairways, platforms, elevated walkways and landings shall be positioned at a
height of _____ (from the bottom of the fixture to the floor directly
beneath). |
Answer: |
|
2.03m |
|
07) |
7 Minimum duration of emergency
lighting in the event of power failure
|
Answer: |
|
1.5hrs. |
|
08) |
Illuminated exit signs shall be
manufactured and installed in accordance with ___________ requirements. |
Answer: |
|
NFPA 101 |
|
09) |
In SAES‐P‐123 lighting standards,
what is the meaning of CRI? |
Answer: |
|
Color Rendering Index |
|
10) |
IN SAES‐P‐123 lighting standards,
what is the meaning of LLF? |
Answer: |
|
Light Loss Factor |
|
11) |
Minimum maintained illuminance level
of Control Room in general 500 Lux (50
fc) |
Answer: |
|
0 |
|
12) |
Minimum maintained illuminance level
of Process Interfaced Buildings |
Answer: |
|
100 Lux (10 fc) |
|
13) |
Minimum maintained illuminance level
of Battery Rooms |
Answer: |
|
300 Lux (30 fc) |
|
14) |
Minimum maintained illuminance level
of Switchgear Rooms |
Answer: |
|
300 Lux (30 fc) |
|
15) |
Minimum maintained illuminance level
of Outdoor Switchyards |
Answer: |
|
20 Lux (2 fc) |
|
16) |
Minimum maintained illuminance level
of General Substation (outdoor) |
Answer: |
|
20 Lux (2 fc) . |
|
17) |
Minimum maintained illuminance level
of General Substation (indoor) |
Answer: |
|
50 Lux (5 fc) |
|
18) |
Minimum maintained illuminance level
of Indoor Substation Operating Aisle |
Answer: |
|
150 Lux (15 fc) |
|
19) |
Minimum maintained illuminance level
of Plant Process Areas |
Answer: |
|
50 Lux (5 fc) |
|
20) |
What is the meaning of CT |
Answer: |
|
Current Transformer |
|
21) |
What is the meaning of VT |
Answer: |
|
Voltage Transformer |
|
22) |
For transformer protection system,
what is the meaning of 51N |
Answer: |
|
Neutral Overcurrent Relay |
|
23) |
For transformer protection system,
what is the meaning of 50/51H |
Answer: |
|
Phase Overcurrent Relay (HV side) |
|
24) |
For transformer protection system,
what is the meaning of 50/51L |
Answer: |
|
Phase Overcurrent Relay (LV side) |
|
25) |
For transformer protection system,
what is the meaning of 50/51G |
Answer: |
|
Ground Overcurrent Relay |
|
26) |
For transformer protection system,
what is the meaning of 87 |
Answer: |
|
Differential Relays |
|
27) |
For transformer protection system,
what is the meaning of 86 |
Answer: |
|
Lockout Relays |
|
28) |
Maximum ampere rating for panel board |
Answer: |
|
400A |
|
29) |
Maximum ampere rating for switch
racks |
Answer: |
|
600A |
|
30) |
Unobstructed horizontal space for
switchgear |
Answer: |
|
Front=2m; back and sides=1m |
|
31) |
Unobstructed horizontal space for
control gear, switchboards, transfer switches, and floor mounted adjustable
frequency drives |
Answer: |
|
Front=1.5m; Sides=1m |
|
32) |
Unobstructed horizontal space for
panel boards, switch racks |
Answer: |
|
Front=1m |
|
33) |
Cables can be used to extend the main
bus of switchgear, control gear, switchboards, switch racks, and panel boards
(TRUE or FALSE) |
Answer: |
|
FALSE |
|
34) |
Maximum control voltage to be used
for motor space heater |
Answer: |
|
24V |
|
35) |
In Switchgear and control equipment
system, What is the meaning of AFD |
Answer: |
|
Adjustable Frequency Drive |
|
36) |
Cable bus shall be used with power
transformers if the forced cooled site rating of the transformer is greater
than ________ |
Answer: |
|
1200A |
|
37) |
Transfer switches shall only be used
in low voltage applications (TRUE or FALSE |
Answer: |
|
TRUE |
|
38) |
Panel boards shall be installed
completely filled with circuit breakers and have ______ spare breakers |
Answer: |
|
0.2 |
|
39) |
Panel boards shall not be installed
in control gear (TRUE or FALSE) |
Answer: |
|
TRUE |
|
40) |
What is the meaning of abbreviation
IEC? |
Answer: |
|
International Electro Technical
Commission |